An S-Trap is an
arrangement which traps water in a return bend, much like a P-Trap,
but has a second return bend into a vertical drain line instead of a
J-Bend into a horizontal drain line. This could also include a
standard P-Trap which connects to a horizontal drain line which turns
down into a vertical drain line without proper venting. In either
case the configuration can cause loss of trap seal through siphonage.
Pipes are filled
with static air. When a flow of water or waste enters the pipe it
displaces the air – pushing it forward down the pipe. As the water
travels down the pipe a vacuum is created behind the flow drawing in
new air, preferably through a vent in the piping system. In the case
of an S-Trap the suction of the water moving down the vertical pipe
pulls the water out of the trap until air can be drawn in through the
drain.
Water closets are
designed to take advantage of this action and are a perfect example
of an S-Trap.
Water passing
through the trap and down the pipe pulls all of the water and waste
out of the bowl until the vacuum is broken by air. Then the tank
valve slowly refills the trap and the bowl so that the seal is
maintained. An S-Trap can work – as in the case of a water closet –
if there is a mechanism to replace the water in the trap, otherwise
the trap flushes and the seal is broken.
Today we rarely
encounter S-Traps except in flushing fixtures. They are forbidden
under the plumbing code. The most common mistake in a plumbing rough
is making the drain arm – from trap to waste stack and vent – too
long. If the top of the waste pipe at the point where it meets its
vent is below the water level (Trap Weir) in the trap, that is
technically an S-Trap – and acts as one causing the trap to siphon.
Since the waste line
requires a minimum grade, the longer the horizontal pipe is the
greater the difference in elevation. Eventually the top of the pipe
at one end is the same elevation as the bottom of the pipe at the
other. This is known as being out of the vent. That is because the
top half of the pipe is helping air pressure balance between the vent
and the trap. When the down side of the pipe gets too low you have
created an S-Trap.
There are instances
where S-Traps are virtually unavoidable. Most often this occurs on
floor drains in a large area such as a commercial kitchen or
warehouse. In these instances long combined waste and vent mains are
used with the top half of the horizontal main acting as a vent. But
as the line gets longer the distance from trap to drain becomes
longer due to grade on the main piping.
Long vertical drops
between drains and traps can cause another problem. The falling water
gains momentum and at a certain point it will have enough momentum to
pass straight through the trap leaving it dry. For that reason the
code restricts the vertical drop to 24”. But what happens when your
main is more than 24” below your drains?
This is one of those
gray areas adjudicated by the local official. If you keep your trap
within the trap weir then the riser to the drain is too long. If you
raise your trap above the main waste/vent then you have created an
S-Trap. Most inspectors prefer the S-Trap. In most instances the
floor drain will be protected with a primer or other means which will
insure the trap seal, so possible siphonage is not an issue, but a
long drop in the vertical pipe will risk even the water from the trap
primer overrunning the trap and leaving it dry.
We often find
situations where piping cannot be installed by the strict letter of
the code. That is why the code allows for the discretion of the
inspector. This is also why it is important, not simply to memorize
the code, but understand the intent of the code.
In our example the
intent is to maintain the trap seal. Using an S-Trap, though
forbidden by code, and a trap primer to insure sealing the trap is
better than a long standpipe, also forbidden by code. By
understanding the reasoning behind the code we can find efficient and
effective installation techniques that solve the problems, or perhaps
– as in the case of the flushable water closet – use the very
problems that caused the S-Trap to be forbidden to design a fixture
that revolutionized sanitary plumbing design.
The plumbing code is
written as a guide to minimum acceptable standards. We should be
working toward best possible practices and standards. To do that we
need to understand why the code is what it is. We must ask ourselves
why something is required or forbidden and then we will know not only
what is required as a minimum, but how we can provide a better
system. If you are chasing best practices instead of minimum
standards you'll never worry about a failed inpection.
One thing to
remember, however, if you are studying for the exam – the exam is
based on the letter of the code and minimum standards. If a vent can
be 1 1/2” by code and you size it 2” you are counted wrong. In
practice there would of course be no problem oversizing a vent, and
the inspector wouldn't say a word, but the test is a test of your
knowledge of the code.
No comments:
Post a Comment